Trane Dehumidifier TCONT802AS32DA User Manual

TCONT802AS32DA Touch Screen and  
TCONT803AS32DA Touch Screen with  
Dehumidification Control Comfort Controls  
18-HD25D19-3  
INSTALLATION INSTRUCTIONS  
APPLICATION  
The TCONT802AS32DA and TCONT803AS32DA Touch Screen Comfort Controls provide electronic control of 24 Vac  
heating and cooling systems. See Table 1 for a general description.  
Table 1. TCONT802AS32DA and TCONT803AS32DA Comfort Control Description.  
Power Method  
Changeover  
Automatic or  
System Selection  
Fan Selection  
Comments  
24 Vac common  
wire  
Heat-Off-Cool-  
Auto (Em. Heat  
for heat pumps)  
On-Auto-Circ  
System and Fan selection  
vary based on system type  
manual selectable  
System and Fan selection  
vary based on System type.  
Humidity sensor to control  
dehumidification.  
Selecting Location  
Install the comfort control about 5 ft. (1.5m) above the  
floor in an area with good air circulation at average  
temperature. See Fig. 1.  
MERCURY NOTICE  
If this control is replacing a control that contains  
mercury in a sealed tube, do not place your old  
control in the trash. Dispose of properly.  
Contact your local waste management authority  
for instructions regarding recycling and the  
proper disposal of the old control.  
NO  
YES  
INSTALLATION  
NO  
When Installing this Product...  
5 FEET  
[1.5 METERS]  
NO  
1. Read these instructions carefully. Failure to follow  
the instructions can damage the product or cause  
a hazardous condition.  
2. Installer must be a trained, experienced service  
technician.  
3. After completing installation, use these instructions  
to check out the product operation.  
M19925  
Fig. 1. Selecting comfort control location.  
U.S. Pat. No. 6595430, D509151, and Other Patents Pending  
69-1790-3  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
HEAT/COOL  
HEAT/COOL  
Y2  
RC  
R
1
RC  
R
Y2  
1
W1  
Y
G
B
W1  
Y
W2  
S1  
S2  
W2  
S1  
G
S2  
B
T
T
2
2
VARIABLE SPEED  
TWO-STAGE  
AIR  
HANDLER  
R
BK  
O
YLO  
G
W1 W2 B/C  
Y
R
Y
G
W2 W3 B/C  
W1  
FURNACE/VARIABLE  
SPEED AIR HANDLER  
INDOOR  
OUTDOOR  
INDOOR  
OUTDOOR  
COOLING UNIT  
O.D. SECTION  
(SINGLE STAGE)  
COOLING UNIT  
O.D. SECTION  
(TWO STAGE)  
ODT  
Y
B
B
Y1 Y2  
(3 PH  
ONLY)  
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
2
FACTORY INSTALLED JUMPER.  
1
2
FACTORY INSTALLED JUMPER.  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M22637  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M22640  
Fig. 7. Typical hookup of two-stage indoor and  
two-stage cooling unit in a single transformer system  
(2H/2C or 2H/1C or 1H/2C).  
Fig. 5. Typical hookup of single-stage heat and cool  
system with single transformer (1H/1C).  
HEAT/COOL  
HEAT/COOL  
RC  
R
Y2  
Y2  
RC  
R
W1  
Y
G
1
W1  
Y
W2  
S1  
S2  
W2  
S1  
S2  
G
B
B
T
T
1
2
3
OIL  
FURNACE  
R
Y
G
W
B/C  
T
T
VARIABLE SPEED  
TWO STAGE  
FURNACE  
R
BK  
O
W1 W2 B/C  
YLO  
Y
G
OIL BURNER PRIMARY  
INDOOR  
OUTDOOR  
INDOOR  
OUTDOOR  
16 SEER  
COOLING UNIT  
O.D. SECTION  
(SINGLE STAGE)  
COOLING UNIT  
O.D. SECTION  
(TWO STEP)  
Y
B
Y2 Y1  
B
(3 PH  
ONLY)  
TO POWER SUPPLY  
PER LOCAL CODES  
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
2
FACTORY INSTALLED JUMPER.  
1
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M22638  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
3
THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.  
M24231  
Fig. 6. Typical hookup of single-stage heat and cool  
system with two transformers (1H/1C).  
Fig. 8. Typical hookup of two-stage indoor and  
two-step scroll cooling unit in a single transformer  
system (2H/2C or 2H/1C or 1H/2C).  
Pub. No. 18-HD25D19-3  
3
69-1790—3  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
HEAT PUMP  
Y2  
F
X2  
RC  
R
O
1
W1  
S1  
S2  
Y
G
B
T
2
I-PF  
PM-A  
SUPPL. HTR.  
CONTROL BOX  
AIR  
R
Y
O
G
W2 W3  
B/C  
T
W1  
HANDLER  
REQ.  
FOR  
3 PH  
ODT-1  
ODT-2  
TO POWER  
SUPPLY PER  
LOCAL  
CODES AND  
AS DEFINED  
IN FIELD  
WIRING TABLE  
INDOOR  
OUTDOOR  
HEAT PUMP  
O.D. SECTION  
O
R
Y
B
X2/BK  
BR(T)  
(SINGLE STAGE)  
(3 PH  
ONLY)  
TO POWER SUPPLY  
PER LOCAL CODES  
1
2
FACTORY INSTALLED JUMPER.  
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE  
ON SELECT MODELS. WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.  
M22641  
Fig. 9. Typical hookup of single-stage heat pump with auxiliary/backup heat (2H/1C heat pump).  
HEAT PUMP  
Y2  
F
X2  
RC  
R
O
1
W1  
S1  
S2  
Y
G
B
T
2
I-PF  
PM-A  
SUPPL. HTR.  
CONTROL BOX  
VARIABLE  
SPEED AIR  
HANDLER  
R
BK  
Y
YLO  
O
W1  
W2 W3  
B/C  
T
G
REQ.  
FOR  
3 PH  
ODT-1  
ODT-2  
TO POWER  
SUPPLY PER  
LOCAL  
CODES AND  
AS DEFINED  
IN FIELD  
WIRING TABLE  
INDOOR  
OUTDOOR  
HEAT PUMP  
O.D. SECTION  
(TWO STAGE)  
BR(T)  
X2/BK  
F
B
Y2  
O
Y1  
R
(3 PH  
ONLY)  
TO POWER SUPPLY  
PER LOCAL CODES  
1
FACTORY INSTALLED JUMPER.  
2
OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. AVAILABLE ON SELECT MODELS.  
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE.  
M22642  
Fig. 10. Typical hookup of multistage heat pump with auxiliary/backup heat (3H/2C heat pump).  
Pub. No. 18-HD25D19-3  
69-1790—3  
4
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
HEAT PUMP  
Y2  
F
RC  
R
1
X2  
W1  
S1  
S2  
O
Y
G
B
T
2
3
VARIABLE SPEED  
AIR HANDLER  
R
R
BK  
O
G
W1 W2 B/C  
Y
YLO  
INDOOR  
OUTDOOR  
16 SEER  
HEAT PUMP  
O.D. SECTION  
(TWO STEP)  
Y2 Y1 O  
B
X2/BK BR(T)  
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
2
FACTORY INSTALLED JUMPER.  
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A CABLE  
SEPARATE FROM THE THERMOSTAT CABLE.  
THE INSTALLER MUST JUMPER AT THE LVTB “R” TO “O”.  
3
M24230  
Fig. 11. Typical hookup of multistage two-step scroll heat pump with auxiliary/backup heat (3H/2C heat pump).  
HEAT PUMP  
RC  
Y2  
1
R
O
F
X2  
Y
W1  
G
B
S1  
S2  
2
T
NON-V.S.  
ONE OR TWO  
STAGE GAS  
FURNACE  
B/C  
Y
W1  
W2  
R
G
INDOOR  
OUTDOOR  
HEAT PUMP  
O.D. SECTION  
(SINGLE STAGE)  
R
Y
O
X2/BK  
BR(T)  
B
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
2
FACTORY INSTALLED JUMPER.  
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A  
CABLE SEPARATE FROM THE THERMOSTAT CABLE.  
M24200  
Fig. 12. Typical hookup of singe-stage heat pump with non-variable speed gas furnace.  
Pub. No. 18-HD25D19-3  
69-1790—3  
5
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
HEAT PUMP  
RC  
Y2  
1
R
O
F
X2  
Y
W1  
G
B
S1  
S2  
2
T
1
VARIABLE  
SPEED  
TWO STAGE  
FURNACE  
R
BK  
O
G
Y
W1  
W2  
B/C  
YLO  
INDOOR  
OUTDOOR  
HEAT PUMP  
O.D. SECTION  
(SINGLE STAGE)  
R
Y
O
BR/X2  
OR BK  
BR(T)  
B
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
2
FACTORY INSTALLED JUMPER.  
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A  
CABLE SEPARATE FROM THE THERMOSTAT CABLE.  
M24201  
Fig. 13. Typical hookup of single-stage heat pump with two stage variable speed gas furnace  
(2H/1C heat pump).  
Pub. No. 18-HD25D19-3  
69-1790—3  
6
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
HEAT PUMP  
RC  
Y2  
1
R
O
F
X2  
Y
W1  
G
B
S1  
S2  
2
T
1
VARIABLE  
SPEED  
TWO STAGE  
FURNACE  
Y1/  
R
BK  
O
G
Y/Y2  
W1  
W2  
B/C  
YLO  
INDOOR  
OUTDOOR  
HEAT PUMP  
O.D. SECTION  
(TWO STAGE)  
R
Y2  
O
X2/BK  
BR(T)  
Y1  
F
B
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
2
FACTORY INSTALLED JUMPER.  
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A  
CABLE SEPARATE FROM THE THERMOSTAT CABLE.  
M24202  
Fig. 14. Typical hookup of multistage heat pump with two stage variable speed gas furnace (3H/2C heat pump).  
Pub. No. 18-HD25D19-3  
7
69-1790—3  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
HEAT PUMP  
RC  
Y2  
1
R
O
F
X2  
Y
W1  
G
B
S1  
S2  
2
T
1
VARIABLE  
SPEED  
TWO STAGE  
FURNACE  
R
BK  
O
G
YLO  
Y
W1  
W2  
B/C  
3
INDOOR  
OUTDOOR  
16 SEER  
R
Y2  
O
X2/BK  
BR(T)  
Y1  
B
HEAT PUMP  
O.D. SECTION  
(TWO STEP)  
(3 PH  
TO POWER SUPPLY  
PER LOCAL CODES  
ONLY)  
1
FACTORY INSTALLED JUMPER.  
OUTDOOR REMOTE SENSOR. WIRES MUST HAVE A  
CABLE SEPARATE FROM THE THERMOSTAT CABLE.  
2
3
M24203  
REMOVE / CUT JUMPER FROM R TO BK.  
Fig. 15. Typical hookup of multistage two-step scroll heat pump with two stage variable speed gas furnace  
(3H/2C heat pump).  
Three AAA alkaline batteries can be used to power the  
comfort control for armchair programming only. To prevent  
the comfort control and heating/cooling system from  
Powering the Comfort Control  
The Comfort Control can be powered with 24 Vac.  
shutting down due to lack of battery power, it is not  
24 Vac Common Power (Recommended)  
recommended that the comfort control be solely powered  
with the three AAA batteries during normal system  
operation. When using batteries, make sure positive and  
negative terminals are oriented correctly, as marked on  
the device. See Fig. 16.  
Wire the common side of the transformer to the B screw  
of the comfort control wallplate. When installing in a single  
transformer system, keep the jumper wire between the R  
and Rc screws. When installing in a two-transformer  
system, use the common from the cooling transformer to  
connect to the B screw and remove the jumper wire  
between the R and Rc screws.  
Battery Power (Optional)  
CAUTION  
Equipment or Property Damage Hazard.  
Using battery power only may not provide  
adequate power to comfort control and can  
cause damage during freezing conditions.  
Connect the 24 Vac Common (B) wire from the  
system transformer to the comfort control for  
proper operation when the battery power is  
drained.  
BATTERIES (3)  
M19918  
Fig. 16. Installing batteries on comfort control back.  
Pub. No. 18-HD25D19-3  
69-1790—3  
8
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
This comfort control is designed to automatically keep the  
current time and day in memory for up to ten years under  
normal use once the calendar is set. When the comfort  
control is first powered, the display is ready for the  
Mounting the Comfort Control  
1. Align the terminal screw blocks with the pins on the  
back of the comfort control.  
2. Push the comfort control straight onto the wallplate.  
calendar date to be entered. See Fig. 19.  
See Fig. 17.  
SET CURRENT DAY  
SET MONTH  
WALL  
MON  
TUE  
WED  
THU  
FRI  
SAT  
SUN  
DONE  
USE ARROWS TO SET YEAR AND TIME  
SLATION  
MOVEDURING  
M22643  
MON  
WED  
THU  
FRI  
SAT  
SUN  
OK TO PICK MULTIPLE DAYS SCREEN LOCKED  
CHANGE FILTER UV LAMP HUMIDIFIER PAD  
Fig. 17. Mounting comfort control on wallplate.  
Adjusting Real-Time Clock  
Setting Calendar and Time  
Locate and remove the tab labeled Remove in the lower  
left corner on the comfort control back. The tab must be  
removed to activate the real-time clock. See Fig. 18.  
DONE  
M22645  
Fig. 19. Setting calendar and time after initial  
powerup.  
REMOVE TAB TO ACTIVATE REAL TIME CLOCK  
IMPORTANT  
The tab on the back of the comfort control in the  
lower left corner must be removed for this  
feature to be active.  
INSTALLATON  
REMOVEDUING  
Using the Comfort Control  
The comfort control has a touch screen interface. Words  
or symbols appear, highlighting the keys, as necessary, to  
complete tasks. Always press the keys with your  
fingertips. Sharp instruments like a pen or pencil point can  
damage the comfort control.  
INSTALLATON  
REMOVEDUING  
1. Use the arrow keys to set the Year, Month and Day,  
as shown in Fig. 19.  
2. Press the Done key.  
M22644  
Fig. 18. Removing tab to activate real-time clock.  
3. Use the arrow keys to set the current time. See  
Fig. 19.  
4. Press the Done key.  
Pub. No. 18-HD25D19-3  
9
69-1790—3  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
OPERATION  
C
F
TO C  
System and Fan Settings  
The System default setting is Heat and the Fan default  
setting is Auto.  
EQUIPMENT  
MONITOR  
TO R  
SYSTEM SETTINGS  
M22646  
Heat: controls heating system.  
Off: heating and cooling are off.  
Cool: controls cooling system.  
Fig. 20. F terminal switch to R (power) side of system  
transformer.  
Auto: automatically changes between heating and cooling  
systems, depending on indoor temperature. (See Installer  
Setup section.)  
Em Heat: emergency heat cycles to maintain  
temperature. Compressor is locked out. (Used only for  
heat pump systems with backup heat.)  
Preprogrammed Settings  
Table 3 shows the default program settings. See Owners’  
Guide for complete instructions on changing the program.  
FAN SETTINGS  
Table 3. Default Program Settings.  
Setpoints  
The Fan setting can be programmed into the comfort  
control schedule for each period (Wake, Leave, Return,  
Sleep). See the Owners’ Guide for additional information.  
Schedule  
Period  
Fan  
Setting  
Time  
6:00AM 70°F  
(21°C)  
8:00AM 62°F  
Heat  
Cool  
Wake  
Leave  
Return  
Sleep  
78°F  
(25.5°C)  
85°F  
Auto  
LED Indication (Requires 24 Vac Common  
Connection)  
An LED indicator is located in the upper right corner of the  
comfort control. It is only visible when lighted:  
Auto  
Auto  
Auto  
(16.5°C) (29.5°C)  
6:00PM 70°F  
(21°C)  
78°F  
(25.5°C)  
It indicates when the comfort control is in the  
Emergency Heat mode. When in Em. Ht. mode, the F  
terminal is continuously energized and the LED is on.  
When the F terminal is wired to an equipment monitor,  
the LED signals when a check or fail signal is sent to  
the comfort control from the system. See Fig. 20. (This  
can occur only when the comfort control is not in Em.  
Ht. mode.)  
10:00PM 62°F  
82°F  
(16.5°C) (28°C)  
Pub. No. 18-HD25D19-3  
69-1790—3  
10  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
INSTALLER SETUP  
The comfort control works with many different system  
types. To operate correctly, the comfort control must be  
set up to operate the installed heating and/or cooling  
system.  
4. Release the two blank keys when the screen on the  
comfort control matches the screen below.  
Follow these steps to enter the Installer Setup:  
1. Be sure the comfort control is powered.  
2. Press and release the System Key.  
THU  
FAN  
ON  
DONE  
Inside  
Set To  
AUTO  
Following  
Schedule  
SYSTEM  
ET  
M22649  
A
M
SCHED HOLD CLOCK SCREE  
M22647  
5. See screen below to review how the comfort control  
keys are used during Installer Setup. See Table 4  
for the Installer Setup Numbers and Settings.  
3. Press and hold the two blank keys on either side of  
the center blank key for approximately five seconds  
until screen changes.  
ADVANCE TO NEXT  
INSTALLER SETUP  
INSTALLER  
SETUP  
NUMBER  
CURRENT  
SETTING  
MO  
TU  
WE  
TH  
FR  
SA  
SU  
Inside  
Set To  
MON  
WED  
THU  
FRI  
SAT  
SUN  
Following  
Schedule  
SYSTE  
M
EM  
HEAT  
OFF  
DONE  
CANC  
DONE  
CHANGE THE  
CURRENT  
SETTING  
PRESS TO EXIT  
INSTALLER SETUP  
M22648  
M22650  
6. Press the Done key to exit the Installer Setup  
screen.  
Pub. No. 18-HD25D19-3  
69-1790—3  
11  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
IMPORTANT  
The Installer Setup Menu (Table 4) shows all the available options. These options customize themselves as  
you make selections to the Installer Setup. Therefore, not all Installer Setup Selections are shown or are avail-  
able to change.  
Table 4. Installer Setup Menu.  
Factory Setting  
Other Choices  
Installer  
Setup  
Number Option  
Select  
Description  
Options  
Description  
Comments  
Not used.  
1 thru  
0099  
Date (Year  
Upper)  
0120  
20  
05  
6
Set first two digits of 21  
current calendar year  
(20 for year 2005, etc)  
21 —first two digits of current 2000 - 2178 available  
calendar year (21xx)  
Date (Year  
Lower)  
0130  
Represents last two 00 -99 Select last two digits of current 2000 - 2178 available  
digits of current  
calendar year (2005).  
calendar year.  
Date (Month) 0140  
Digit(s) represents  
current calendar  
month.  
1-12  
Select number that represents  
current calendar month.  
Date  
(Day)  
0150  
0160  
15  
4
Digit(s) represents  
current calendar date.  
1-31  
0
Select number that represents  
current calendar date.  
Schedule  
Options  
7-day programming  
0—nonprogrammable  
System Type 0170  
Selection  
1
1 Heat/1Cool  
1-12  
1—1heat/1cool  
2—single-stage heat pump (no defaults vary by  
aux. heat)  
3—heat only (no fan)  
4—heat only (with fan)  
Available options and  
comfort control.  
System selection  
automatically  
5—hot water Series 20 (3-wire modifies some  
or normally open zone valves) default settings and/  
6—cool only  
7—2 heat/1cool heat pump  
8—2 heat/2 cool  
or hides other  
Installer Setup  
options.  
9—2 heat/1cool  
10—1 heat/2 cool oil furnace  
or 0H/2C  
11—2 heat/2 cool heat pump  
(with no auxiliary heat)  
12—3 heat/2 cool heat pump  
(with auxiliary heat)  
Fan Operation 0180  
0
Heat/Cool  
1
Heat pump or electric heat  
applications where comfort  
control controls fan operation selected. If heat  
Only shown if heat/  
cool system is  
applications where  
equipment controls  
fan operation in heat  
mode.  
in heat mode.  
pump is chosen, fan  
defaults to electric.  
Backup Heat 0200  
Source  
(Auxiliary  
0
1
Heat pump backup  
heat source is electric.  
1
0
Heat pump backup heat  
source is fossil fuel.  
Only shown if 2 heat/  
1 cool or 3 heat/2  
cool heat pump is  
chosen.  
Heat)  
External  
0210  
External fossil fuel kit  
is controlling heat  
pump backup heat  
(recommended)  
No external fossil fuel kit is  
controlling heat pump backup fuel is chosen as  
heat. This comfort control  
controls the backup fossil fuel  
heat with outdoor sensor.  
Only shown if fossil  
Fossil Fuel Kit  
backup heat source.  
Cycles per  
hour (cph) for  
1st Stage  
0220  
0230  
3
3
Compressor Stage 1 1-6  
cycles per hour (cph)  
1-6 available;  
3 is recommended.  
Compressor  
Cycles per  
hour (cph) for  
2nd Stage  
Compressor Stage 2 1-6  
cycles per hour (cph)  
1-6 available;  
3 is recommended.  
Only shown if two  
stages of cool are  
selected.  
Compressor  
Pub. No. 18-HD25D19-3  
69-1790—3  
12  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
Table 4. Installer Setup Menu. (Continued)  
Factory Setting  
Other Choices  
Installer  
Setup  
Number Option  
Select  
Description  
Options  
Description  
Comments  
Cycles per  
hour (cph) for  
1st Stage  
Heat  
0240  
0250  
0260  
5
5
9
9
Heat Stage 1 cycles 1-12  
per hour (cph)  
1-12 available; typical settings: Not shown if system  
1—1 cph used for steam or  
gravity system.  
3—3 cph used for 2-stage  
selection is heat  
pump. Selection in  
this stage changes  
fossil fuel forced air systems or default cph for 2nd  
hot water systems.  
stage heat.  
5—5 cph used for single-stage  
fossil fuel forced air systems.  
9—9 cph used for electric  
forced air heat systems  
(electric auxiliary heat for heat  
pump systems).  
Cycles per  
hour (cph) for  
2nd Stage  
Heat  
Cycles per hour (cph) 1-12  
for 2nd Stage Heat or  
Auxiliary Heat for  
2 H/1C Heat Pump  
Systems  
1-12 available; typical settings: Only shown if two  
1—1 cph used for steam or  
gravity system.  
stages of heat are  
selected.  
3—3 cph used for 2-stage  
fossil fuel forced air systems or  
hot water systems.  
5—5 cph used for single-stage  
fossil fuel forced air systems.  
9—9 cph used for electric  
forced air heat systems  
(electric auxiliary heat for heat  
pump systems).  
Cycles per  
hour (cph) for  
3rd Stage  
Heat  
Cycles per hour (cph) 1-12  
for Auxiliary Heat in  
3H/2C Heat Pump  
Systems  
1-12 available; typical settings: Only shown if 3H/2C  
1—1cph used for steam or  
gravity system.  
heat pump system is  
selected.  
3—3 cph used for 2-stage  
fossil fuel forced air systems or  
hot water systems.  
5—5 cph used for single-stage  
fossil fuel forced air systems.  
9—9 cph used for electric  
forced air heat systems  
(electric auxiliary heat for heat  
pump systems).  
Cycles per  
hour (cph) for  
Em Heat  
0270  
Cycles per hour (cph) 1-12  
for Emergency Heat  
1-12 is available; typical  
settings:  
3—3 cph used for 2-stage  
Only shown if 2 heat/  
1 cool or 3 heat/2  
cool heat pump is  
fossil fuel forced air systems or selected.  
hot water systems.  
5—5 cph used for single-stage  
fossil fuel forced air systems.  
9—9 cph used for electric  
forced air heat systems  
(electric auxiliary heat for heat  
pump systems).  
Continuous  
Backlight  
0280  
0
0
Backlight not on  
continuously. Comfort  
control backlight  
comes on with each  
key press.  
1
1
Backlight is on continuously  
(comfort control must have a shown; however,  
common wire attached for this continuously on  
Option is always  
function).  
backlight works only if  
comfort control is  
wired with 24 Vac  
Common.  
Changeover 0300  
Manual changeover  
1—auto changeover  
Pub. No. 18-HD25D19-3  
69-1790—3  
13  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
Table 4. Installer Setup Menu. (Continued)  
Factory Setting  
Other Choices  
Installer  
Setup  
Number Option  
Select  
Description  
Options  
Description  
Comments  
Deadband  
0310  
2 thru 9 Heating and cooling  
setpoints can be set  
no closer than chosen  
value:  
3
Heating and cooling setpoints Shown only if  
can be set no closer than 3°F automatic  
(1.5°C).  
changeover is  
selected.  
2—2°F (1°C)  
3—3°F (2°C)  
4—4°F (2.5°C)  
5—5°F (3°C)  
The deadband is  
restricted to the range  
of 5 to 9 if ISU 0380 is  
set to  
6—6°F (3.5°C)  
7—7°F (4°C)  
dehumidification  
droop control.  
8—8°F (4.5°C)  
9—9°F (5°C)  
Temperature 0320  
Indication  
Scale  
0
1
Temperature is  
displayed in °F.  
1
Temperature is displayed in °C.  
Daylight  
Savings  
0330  
Daylight savings  
enabled (use through  
2006 and for areas  
that do not use the  
new 2007 DST  
0, 2  
0—daylight savings is  
disabled.  
2—daylight savings is enabled savings.  
(start using in 2007, for areas  
that use the new 2007 DST  
calendar).  
Set to 0 in areas that  
do not follow daylight  
calendar).  
Remote  
Temperature  
Sensor  
(Outdoor or  
Indoor)  
0340  
0
No remote  
temperature sensor  
1-3  
1—outdoor temperature  
sensor for display only.  
2—outdoor temperature  
sensor for system control,  
used for select heat pump  
systems. (See Special Heat  
Pump Features section for  
more details.)  
Defaults and Options  
depend on System  
Type selection.  
Indoor Temperature  
Sensor uses an  
averaging network  
and does not include  
on-board sensor.  
3—indoor temperature sensor  
Heat Pump  
Compressor  
Lockout  
0350  
0
0
No compressor  
lockout.  
15, 20, 15°F (-9.5°C)  
25, 30, 20°F (-6.5°C)  
35, 40, 25°F (-4°C)  
Default depends on  
other selections.  
Shown if Outdoor  
Temperature for  
45  
30°F (-1°C)  
35°F (1.5°C)  
40°F (4.5°C)  
45°F (7°C)  
control is selected.  
Heat Pump  
Auxiliary  
Lockout  
0360  
0380  
No heat pump  
auxiliary lockout.  
40, 45, 40°F (4.5°C)  
50, 55, 45°F (7°C)  
Shown if electric is  
chosen for backup  
heat source and  
outdoor temperature  
sensor for control is  
selected.  
60  
50°F (10°C)  
55°F (13°C)  
60°F (15.5°C  
Indoor  
Dehumidifica-  
tion Control  
0
0
No indoor  
dehumidification  
control.  
1
1—dehumidification droop  
control.  
Available on models  
with humidity sensor.  
Furnace Filter 0500  
Change  
Reminder  
Furnace filter change 1-6  
reminder off.  
1—10 run time days  
2—30 run time days  
3—60 run time days  
4—90 run time days  
5—120 run time days  
6—365 run time days  
Run time based on  
call for fan.  
Humidifier  
Pad  
Replacement  
Reminder  
0510  
0
Humidifier pad  
replacement reminder  
off.  
1-3  
1—90 calendar days  
2—180 calendar days  
3—365 calendar days  
Pub. No. 18-HD25D19-3  
69-1790—3  
14  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
Table 4. Installer Setup Menu. (Continued)  
Factory Setting  
Other Choices  
Installer  
Setup  
Number Option  
Select  
Adaptive  
Intelligent  
Description  
Options  
Description  
Comments  
0530  
1
Adaptive Intelligent  
Recovery™ control is  
activated (system  
0
0—conventional recovery  
(system starts recovery at  
programmed time)  
Recovery™  
starts early so setpoint  
is reached by start of  
program period).  
Number of  
Periods  
0540  
4
Four periods available 2  
(Wake, Leave, Return,  
Sleep)  
Two periods available (Wake Not shown if  
and Sleep) non-programmable is  
selected. 2 or 4  
applies to all days of  
the week.  
Minimum  
Compressor  
Off Time  
0580  
0600  
0610  
5
Five minute minimum 0, 2, 3, Minimum number of minutes Five minutes  
off time for  
compressor.  
4
compressor is off between  
calls for compressor.  
recommended  
Heat  
Temperature  
Range Stop  
90  
50  
Highest heating  
setpoint.  
40 to 89 Temperature range (1°F  
increments) of heating  
setpoint.  
Shown in 1/2 °C.  
Cool  
Temperature  
Range Stop  
Lowest cooling  
setpoint.  
51 to 99 Temperature range (1°F  
increments) of cooling  
setpoint.  
Shown in 1/2 °C.  
Clock Format 0640  
12  
0
12-hour clock format 24  
24-hour clock format  
Extended Fan 0650  
on time Heat  
No extended fan  
operation after call for  
heat ends.  
90  
Fan operation is extended 90 Not shown if fan  
seconds after call for heat  
ends.  
operation is set to  
fossil fuel or in Cool  
Only Systems  
Extended Fan 0660  
on time Cool  
0
0
No extended fan  
operation after call for  
cool ends.  
90  
Fan operation is extended 90 Not shown in Heat  
seconds after call for cool  
ends.  
Only Systems.  
Keypad  
Lockout  
0670  
Unlocked keypad  
1, 2  
1—partially locked keypad  
2—fully locked keypad  
Unlocked—all  
functions are  
available.  
Partially locked—only  
temperature up and  
down keys and ability  
to enter and modify  
Installer Setup mode  
are available. Fully  
locked—only ability to  
enter and modify  
Installer Setup mode  
are available.  
Pub. No. 18-HD25D19-3  
69-1790—3  
15  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
Table 4. Installer Setup Menu. (Continued)  
Factory Setting  
Other Choices  
Installer  
Setup  
Number Option  
Select  
Description  
Options  
Description  
Comments  
Temperature 0680  
Control in  
Heat  
2
Standard temperature 1, 3  
control in heating.  
1—less aggressive  
temperature control (could  
cause temperature  
undershoot)  
Applies to recovery  
ramp and use of  
auxiliary heat during  
recovery.  
3—more aggressive  
temperature control (could  
Choose 1 if getting  
temperature  
cause temperature overshoot) overshoot.  
Choose 3 if getting  
temperature  
undershoot.  
Temperature 0690  
Control in  
Cool  
2
Standard temperature 1, 3  
control in cooling.  
1—less aggressive  
temperature control (could  
cause temperature  
undershoot)  
Applies to recovery  
ramp.  
Choose 1 if getting  
temperature  
3—more aggressive  
temperature control (could  
overshoot.  
Choose 3 if getting  
cause temperature overshoot) temperature  
undershoot.  
Temperature 0700  
Display Offset  
0
0
No difference in  
displayed temperature -1, 0, 1, -2°F (-1°C)  
and actual room  
temperature.  
-3, -2, -3°F (-1.5°C)  
2, 3  
-1°F (-0.5°C)  
0°F (0°C)  
1°F (0.5°C)  
2°F (1°C)  
3°F (1.5°C)  
ResetComfort 0710  
Control  
No comfort control  
reset.  
1
Resets all Installer Setup  
Options to default values and settings and time are  
Only calendar  
resets schedule to default  
setting.  
retained.  
Pub. No. 18-HD25D19-3  
69-1790—3  
16  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
SYSTEM CHECKOUT  
Installer System Test  
CAUTION  
Minimum compressor off-time is bypassed  
during Installer System Test.  
The Installer System Test mode is used to test the HVAC  
system(s). See Table 5. While in System Test mode,  
minimum off-time for compressors is bypassed.  
Equipment Damage Hazard.  
The Installer Test is part of the Installer Setup options.  
Enter Installer Setup screen and press the Down arrow  
key to bring up test selection(s) quickly.  
Avoid cycling compressor quickly.  
Table 5. System Test(s).  
Factory Setting Other Choices  
Description  
Installer  
Setup  
Number Options  
Select  
Description  
Options  
Comments  
Installer  
Test Cool  
Test 1  
0
Cool is off  
1,2  
0—cool off  
1—cool stage 1 turns on  
System selection  
determines which  
2—cool stages 1 and 2 on tests are available  
and the number of  
stages shown.  
Installer  
Test Fan  
Test 2  
Test 3  
0
0
Fan is off  
Heat is off  
1
0—fan off  
1—fan turns on  
Installer  
1-3  
0—heat off  
Test Heat  
1—stage 1 heat on  
2—stages 1 and 2 heat on  
3—stages 1, 2 and 3 (Aux  
Ht) on  
Installer  
Test Em  
Ht  
Test 4  
0
Emergency  
heat is off  
1
0—emergency heat off  
1—emergency heat on  
2—emergency heat and  
auxiliary heat turn on  
Available only if  
heat pump with  
auxiliary heat is  
selected.  
Pub. No. 18-HD25D19-3  
69-1790—3  
17  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
ADVANCED FEATURES  
3. Choose Outdoor Temperature Sensor for  
Control Option in Installer Setup Number 0340.  
4. Choose Compressor Lockout Temperature in  
Installer Setup Number 0350.  
5. Choose Auxiliary Lockout Temperature in  
Outdoor or Indoor Temperature Sensor  
For accuracy, the initial reading of the indoor and outdoor  
temperature sensors require five minutes to stabilize. See  
the Sensor instructions for installation information.  
Installer Setup Number 0360.  
Special Heat Pump Features  
NOTE: There is a 5°F deadband between the Compres-  
sor and Auxiliary Heat Lockout Temperatures  
Heat Pump with Fossil Fuel Auxiliary Heat (Dual  
Fuel) and Outdoor Temperature Sensor  
In this operation there is no external fossil fuel kit (dual  
OPERATION IN HEAT MODE  
When the outdoor temperature is below the Compressor  
Lockout Temperature, only the Auxiliary Heat operates.  
fuel kit) installed; the comfort control controls this function.  
When the outdoor temperature is above the Auxiliary  
1. Choose correct heat pump application in Installer  
Lockout Temperature, only the Compressor operates.  
Setup Number 0170.  
See Fig. 21.  
2. Choose Fossil Fuel Option as the backup heat  
source in Installer Setup Number 0200.  
3. Choose No External Fossil Fuel Kit Option as  
controlling backup heat in installer Setup Number  
0210.  
COMPRESSOR ONLY  
AUXILIARY  
4. Outdoor Temperature Sensor for Control Option  
is automatically chosen in Installer Setup Number  
0340.  
5. Choose appropriate Balance Point Temperature  
in Installer Setup Number 0350.  
50  
35  
LOCKOUT  
TEMPERATURE  
BOTH COMPRESSOR AND  
AUXILIARY HEAT  
COMPRESSOR  
LOCKOUT  
TEMPERATURE  
AUXILIARY ONLY  
OPERATION IN HEAT MODE ABOVE BALANCE POINT  
(OUTDOOR TEMPERATURE)  
M19950  
When the outdoor temperature is above the selected  
Balance Point Temperature (ISU 0350), only the  
compressor operates and the fan (G terminal) energizes  
when the comfort control calls for heat.  
Fig. 21. Heat Pump Operation with Lockout  
Temperatures Set.  
When the outdoor temperature is between the two  
temperatures, both the Compressor and Auxiliary Heat  
operate.  
OPERATION IN HEAT MODE BELOW BALANCE POINT  
(OUTDOOR TEMPERATURE)  
When the outdoor temperature is below the selected  
Balance Point Temperature (ISU 0350), only the Fossil  
Fuel (auxiliary heat) operates and the fan (G terminal)  
does not energize when the comfort control calls for heat.  
OPERATION IN THE EMERGENCY HEAT MODE  
Once the comfort control is placed into the Emergency  
Heat mode, the compressor and auxiliary lockout features  
are turned off. In the Emergency heat mode, the  
compressor is locked out. The first stage of heat is  
whatever is connected to the X2 terminal. The second  
stage of heat is connected to the W1 terminal. Usually the  
emergency and auxiliary heat sources are electric strip  
heat in these cases.  
OPERATION IN EMERGENCY HEAT MODE  
The balance point (outside) temperature is not used in the  
Emergency heat mode. When the comfort control is  
moved to the Emergency Heat position, the compressor is  
locked out. The first stage of heat is whatever is  
connected to the X2 terminal. The second stage of heat is  
what is connected to the W1 terminal. Often there is only  
one source of non-compressor heat and the X2 terminal is  
jumpered to the W1 terminal.  
Dehumidification Droop Control  
The dehumidification control attempts to control to the  
user's humidity setpoint by turning on the air conditioner.  
In extremely high humidity conditions, the comfort control  
°
keeps the air conditioner running for up to 3 F below the  
Heat Pump with Electric Auxiliary (Backup) Heat  
and Outdoor Temperature Sensor  
1. Choose correct heat pump application in Installer  
Setup Number 0170.  
temperature setpoint. It does this while trying to achieve  
the desired humidity setpoint and balancing that with the  
temperature setpoint.  
2. Choose Electric as Auxiliary (Backup) Heat  
Source in Installer Setup Number 0200.  
Pub. No. 18-HD25D19-3  
69-1790—3  
18  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
TROUBLESHOOTING (SEE TABLE 6)  
Table 6. Troubleshooting.  
Symptom  
Possible Cause  
Action  
Display does not come on.  
Comfort control is not being  
powered.  
Check for 24 Vac between B and Rc.  
Temperature settings do not  
change.  
The upper or lower temperature  
limits were reached.  
Check temperature setpoints.  
Check Installer Setup Numbers 0600 and  
0610; modify as needed.  
The keypad is fully locked.  
Check Installer Setup Number 0670 to  
change keypad locked options.  
Heating or cooling does not come  
on.  
Comfort control minimum off-  
time is activated.  
Wait up to five minutes for the system to  
respond.  
System selection is not set to  
Heat or Cool.  
Set system Selection to correct position.  
System type Selection is  
incorrect.  
Check Installer Setup Number 0170 and  
make sure correct System type is  
chosen.  
Comfort control is calling for Heat  
(Heat on) or Cool (Cool on) but no  
heating or cooling is running.  
Heating or cooling equipment is  
not operating.  
Check wiring.  
Check Installer Setup Number 0170 and  
make sure correct system type is chosen.  
Verify operation of equipment in System  
Test mode.  
Comfort control does not respond  
when touch areas are pressed.  
The keypad is locked.  
Check Installer Setup Number 0670 to  
change keypad locked options.  
Pub. No. 18-HD25D19-3  
69-1790—3  
19  
 
TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION  
® U.S. Registered Trademark  
© 2006 American Standard Inc.  
All Rights Reserved  
American Standard Inc.  
Troup Highway  
Tyler, TX 75711-9010  
Pub. No. 18-HD25D19-3  
69-1790—3 M.S. Rev. 01-06  
 

Teledyne Marine Instruments 5499 User Manual
Therma Stor Products Group Heating System PN 4027300 User Manual
The Singing Machine Microphone SMC4TV Mic User Manual
Toshiba TV VCR Combo MV13Q41 User Manual
UNICOM Electric Switch GEP 32005T User Manual
Universal Smoke Alarm SS 901 LR User Manual
Univex Washer 800 series User Manual
ViewSonic Digital Photo Frame DF88W 523 User Manual
Vivotek Security Camera IP8161 User Manual
VXI Headphones P41TR User Manual